본문 바로가기

Indicating and Switch

T931, T932_Indicating temperature switch

T931 (Case compensation system SAMA class ⅢB) T932 (Full compensation system SAMA class ⅢA)

Service intended

This temperature switch is installed with a micro contact and it is suitable for measuring the temperature of corrosive fluid. Dead band is fixed.

Nominal diameter 150 mm
Repeatability ±1.0 % of adjustable range
Accuracy ±2.0 % of full scale
Measuring system Organic gas : 0 ~ 200 °C (Only T932)
Inert gas : -200 ~ 700 °C
Working range Maximum scale value

Standard features

Location of stem and mounting Bottom connection, surface, case mounting
Case Silver gray finished aluminium
Cover Silver gray finished aluminium
Window Instrument glass
Switch type Micro switch snap action
Switch form One SPDT for single setpoint
Two SPDT for dual setpoint
Capillary Capillary : 1.6/0.2 mm, 316SS
Armored tube : 7.5/5.5 mm, 304SS
Contacts AC 125 V / 250 V, 15 A
DC 125 V, 0.4 A for resistance load
DC 125 V, 0.03 A for inductive load
Conduit connection ½", ¾" PF
Stem 8.0, 10.0 and 12.0 mm
316SS and 316L SS
Stem, process connection ⅜", ½", ¾" PT, NPT and PF
Option Special accuracy : ±1.0 % of full scale

© WISE Control Inc. All rights reserved. ALL PRODUCT, PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, FUNCTION OR DESIGN OR OTHERWISE.

Download

CATALOG

MANUAL

HOW TO ORDER

Attached files

공유하기


맨 위로 이동